Fluke 1770 series three-phase Power Quality Analyzers

Features

  • Automatically measures parameters for power and power quality
  • Mains power quality status at a glance for faster troubleshooting
  • Simple display of data on V/A/Hz, power, decreases, increases and harmonics
  • Record fast transients of up to 8 kV
  • Power supply directly from measuring circuit without a power cord
Category: Tag:

The Fluke 1770 Series three-phase Power Quality Analyzers are designed as the faster and easier way to analyse mains power quality, offering automatic measurements, a simple user interface and setup, best-in-class specifications and a simplified reporting platform. The instrument can also be powered directly from the measurement circuit, eliminating the need to find a socket or use a long extension cord. Find out how to detect energy waste by managing grid power quality here.

With the Fluke 1770 series of three-phase Power Quality Analyzers, you'll never miss another critical power quality event - from fast transients up to 8 kV, harmonics up to 30 kHz, voltage fluctuations and the voltage,current and power measurements that allow you to characterise your electrical system.

Advantages:

- Automatically measures and records important power quality parameters (harmonics, voltage fluctuations, unbalance, inrush current, etc.).
- Bright, large touchscreen with physical navigation buttons and optimised user interface.
- Guided set-up procedure for fast and safe installation, including the ability to automatically digitally correct measurement connections without changing the physical probe connections.
- Ability to set custom views for quick access to the tests and data most important to you
- Flexibility in data transfer (e.g. PC to USB, Wi-Fi, mobile connection, USB direct), without interrupting your power quality or energy analysis.
- Renewed software package (Energy Analyze Plus) for modern, intuitive data analysis and reporting.

Powerful analysis software with easy report creation

Fluke 1770 series three-phase Power Quality Analyzers come standard with the powerful Fluke Energy Analyze Plus software, designed to eliminate the problems found with other multi-function application software. Energy Analyze Plus helps you evaluate power quality data. You do not need extensive training and can start using it immediately.

Energy Analyze Plus makes downloading, analysing, tracking and reporting grid quality and energy data easier than ever. Quickly compare results to historical values, compare them to industry standards, compare measured data to local conditions and create a more complete picture of what's happening in your facility, even as the data is still being collected. Energy Analyze Plus provides integrated support for the Fluke 1730-, 1740- and 1770-series energy loggers and Power Quality Analyzers.

  • “In workshop” and “on site” set-up and download via PC application software
  • Easily download data with a USB memory stick, WiFi, LTE, wired Ethernet or USB cable
  • Analyse every measured detail of energy consumption and power quality condition with automatic reports
  • One-touch reports: create standardised reports compliant with common standards such as EN 50160, IEEE 519, GOST 33073 IEC 61000-2-2 or export data in a PQDIF or NeQual compliant format or .csv for use with third-party software
  • With advanced analysis, the user can choose any available logged parameter and create a highly customised display of measurements for advanced data correlation
Applications 1773 1775 1777
Energy inspections and tax tests - - -
Harmonic research - - -
Cut-off by circuit breaker   - -
Power company grid power quality surveys   - -
Detection of equipment failures caused by transients   - -

 

Key features

Voltage inputs
Number of inputs 4 inputs, 3 phases and neutral with respect to PE (5 connectors)
Measurement category 1000 V CAT III / 600 V CAT IV
Maximum input voltage 1000 V RMS / 1000 V DC (1700 Vpk)
Nominal voltage range Star and single-phase: variable (50 V - 1000 V)
Triangle: variable (100 V - 1000 V)
Complies with IEC 61000-4-30 Class A for rated voltages (Vdin) 100 V - 690 V
Input impedance 10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE
Bandwidth DC to 30 kHz for PQ measurements, excluding transients
Resolution 24-bit synchronous sampling
Sample frequency 80 kS/s at 50/60 Hz
Scale setting 1:1, variable for use of voltage transformers
Voltage transients
Measuring range ±8 kV
Sample rate 1775: 1 MS/s
1777: 1 MS/s, 20 MS/s
Bandwidth DC up to 1 MHz
Trigger Adjustable trigger level. Triggers on high-frequency components > 1.5 kHz
Resolution 14-bit synchronous sampling
Power inputs
Number of inputs 4 inputs (3 phases and neutral), mode is automatically selected for connected sensor
Reach AC 1 A to 1500 A with i17XX-FLEX1500 12
1 A to 1500 A with i17XX-FLEX1500 24
3 A to 3000 A with i17XX-FLEX3000 24
6 A to 6000 A with i17XX-FLEX6000 36
40 mA to 40 A with clamp i40s-EL
4 A to 400 A with clamp i400s-EL
DC 20 A to 2000 A with 80i-2010-EL current clamp
Bandwidth DC up to 30 kHz
Resolution 24-bit synchronous sampling
Sample frequency 80 kS/s at 50/60 Hz
Scale setting 1:1 variable
Input voltage Current clamp: 50 mV / 500 mV rms; CF 2.8
Rogowski coil: 15 mV / 150 mV rms at 50 Hz, 18 mV / 180 mV rms at 60 Hz; CF 4
all within nominal probe range
Input impedance 11 kΩ
Auxiliary inputs
Wired connection with 17xx-AUX adapter
Number of inputs 2
Input range Direct: 0 V DC to ± 10 V DC
0 V to 1000 V DC
Input impedance Direct: 2.92 MΩ
Scale factor Format: mx + b (gain and deviation) user-configurable
Displayed units User-configurable (up to 8 characters, e.g. °C, psi, or m/s)
Voltage and current for data acquisition
Power input frequency DC, 50/60 Hz 15% (42.5 Hz ... 57.5 Hz, 51 Hz ... 69 Hz)
Topologies 1-φ, 1-φ IT, split phase, 3-φ triangle, 3-φ star IT, 3-φ Aron/Blondel (2-element triangle), 3-φ triangle open branch, 3-φ triangle high branch
Data storage Fluke 1773/1775: 8 GB internal (expandable with microSD card)
Fluke 1777: 32 GB microSD card (installed)
Memory Normally 10 log sessions of 8 weeks with 1-minute intervals and 100 events.
The number of possible logging sessions and the logging period depend on user requirements
Accuracy in real time Internal: 3 ppm (0.26 s per day, 8 s per month)
NTP (internet time): Depends on internet latency, usually < 0.1 s absolute for UTC
GPS: < 1 ms absolute for UTC
Trend interval
Measured parameter See operating instructions
Trend interval User-selectable: 1 sec, 3 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Average interval for minimum/maximum values Voltage, current: ½ cycle RMS (20 ms at 50 Hz, 16.7 ms at 60 Hz)
Aux, power: 200 ms
Total harmonic distortion Total harmonic distortion of voltage and current is calculated based on 50 harmonics
Measurements mains power quality
Measured parameter See operating instructions
Harmonischen h0 ... h50
% fund and RMS for voltage, current and power
Phase angles for voltage and current up to h11
Interharmonischen ih0... ih50
% fund and RMS for voltage and current
Supraharmonischen 2-9 kHz with 200 Hz bins
9-30 kHz with 2 kHz bins
RMS for voltage and current
Measurement method for harmonics Grouped, subgrouped and single harmonic bins according to IEC 61000-4-7.
Method automatically selected based on configured PQ standard or user-configurable.
Total harmonic distortion Calculated for up to 50 harmonics (depending on selected PQ standard)
Signals superimposed on the mains voltage (mains signalling) 2 frequencies in the range of 110 Hz to 3000 Hz
Events Tension Voltage fluctuations, interruptions and rapid voltage changes, mains voltage signals, anomalous waveforms, transients
Current Inrush current
Triggered registrations Half cycle RMS of voltage and current for 10 s
Waveform of voltage and current for 10/12 cycles
Signals on mains: 200 ms RMS of signals on mains up to 120 s
Transients: Waveform of voltage
(Fluke 1777: 1 MS/s or 20 MS/s, 500,000 points, Fluke 1775: 1 MS/s, 25,000 points)
Compliance with standards
Power IEEE 1459
Harmonischen IEC 61000-4-7: Class 1
IEEE 519 (short and very short harmonics)
Flicker IEC 61000-4-15 class F1
Mains power quality IEC 61000-4-30 class A, IEC 62586 PQI-A-PI
Network power quality compliance EN 50160 + GOST + NEQUAL + NETCODE + FOL
Interfaces
Ethernet 1 Gbit/s 1000BASE-T
USB type A USB 2.0 high-speed for USB flash drives for measurement data transfer, firmware updates and licence installation. Max. supply current: 500 mA
USB-C USB 2.0 high speed for downloading data to PC and calibration (USB Type A to USB-C or USB-C to USB-C cable required)
Auxiliary power supply for the analyser (USB C power adapter PD 2.0 or higher supporting 9 V 1.8 A required)
USB 3.0 super-speed for USB-C flash drives for measurement data transfer, firmware updates and licence installation. Max. supply current: 900 mA
WiFi/BLE module1 802.11 ac 2.4 GHz / 5 GHz, support for simultaneous access point and client mode
Bluetooth 5.0/BLE
Antenna: Internal and external2
LTE/4G module3 LTE-A Cat 12
global LTE-A and UMTS/HSPA+ coverage:
Antenna: External2
GPS MCX connector for connecting a GNSS antenna for GPS/GLONASS2
1 Not in 177X/BASIC versions
2 Requires a 5 m extension cable, Fluke part number 5263915
3 Availability and supported providers vary by country. Please contact your local Fluke representative.

Electrical measurement accuracy

Parameter Reach Resolution Intrinsic accuracy under reference conditions
% of readout + % of full scale
Tension 1000 V 0,1 V 0.1% of rated voltage
in accordance with
IEC 61000-4-30 class A1,2
±(0.04% + 0.004%)3
Voltage fluctuations - 0,1 V 0.2% of Vnom1,2
Voltage transients ±8 kVpk - ±5% +0.25%)
Voltage harmonics/interharmonics 100% 0.1 % / 0.1 mV ≥ 1% Vnom1: ± 2.5% from readout.
<1 % Vnom1: ± 0.025 Vnom
THD voltage 100% 0.1 % / 0.1 V ±(2.5 % + 0.5 %)
Voltage distortions 2-9 kHz Max 100 V 0.1 mV ± (2.5% + 0.1 V)
Voltage distortions 9-30 kHz Max 100 V 0.1 mV ± (2.5% + 0.1 V)
Current
(Rogowski current mode)
With iFlex 1500 A,
i17XX-FLEX1500 24
150 A
1500 A
0,01 %
0,1 A
±(1 % + 0.02 %)
With iFlex 3000 A,
i17XX-FLEX3000 24
300 A
3000 A
0,01 A
0,1 A
±(1 % + 0.03 %)
With iFlex 6000 A,
i17XX-FLEX6000 36
600 A
6000 A
0,1 A
1 A
±(1.5 % + 0.03 %)
With AC current clamp 40 A,
i40s-EL
4 A
40 A
0,001 A
0,01 A
±(0.7 % + 0.02 %)
With AC current clamp 400 A,
i400s-EL
40 A
400 A
0,01 A
0,1 A
±(2% + 0.2%)
±(0.7% + 0.1%)
With AC/DC current clamp
2000 A, 80i-2010s-EL
200 A
2000 A
0,01 A
0,1 A
±(0.8 % + 0.2 %)
Current, min/max 100% defined by accessory X2 of intrinsic accuracy
Voltage harmonics/interharmonics 100% 0.1% / 0.01 A ≥ 3% from Inom: ±2.5% from readout. 4
<3% by Inom: ± 0.15% by Inom
THD current 100% 0,1% ±(2.5 % + 0.5 %)
Frequency 42.5 Hz ... 69 Hz 0.001 Hz ±0.01 Hz
Tension imbalance 100% 0,1% ± 0.15 %
Current imbalance 100% 0,1% ± 0.15 %
Flicker Pinst, Pst, Plt 0 to 20 0,01 5 %
Signal voltage from mains Up to 3 kHz
0-15% by Vnom
0.1 V / 0.1% 1-3% of Vnom: ±0.15% of Vnom
3-15% Vnom: ± 5% from readout.
AUX input ±10 V 0.1 mV ±(0.2 % + 0.05 %)
1 Rated voltage in the range 100 V to 690 V; also known as Udin.
2 0 °C to 45 °C: Intrinsic accuracy x2. Outside 0 °C to 45 °C: Intrinsic accuracy x3
3 For calibration laboratories only
4 With iFlex 1500A, I17XX-FLEX1500 24

Power/energy

Parameter Direct input1 Current clamp i40S-EL
Power range W, VA, var Current clamp: 50 mV / 500 mV
Rogowski: 15 mV / 150 mV
4 A / 40 A
Current clamp: 50 W / 500 W
Rogowski: 15 W / 150 W
4 kW / 40 kW
Max. resolution W, VA, var 0,1 W 1 W / 10 W
Phase (voltage to current)1 ±0,2° ±1°
Parameter iFlex 1500A, I17XX-FLEX1500 24 iFlex 3000A, I17XX-FLEX3000 iFlex 6000A, I17XX-FLEX6000
Power range W, VA, var 150 A / 1500 A 300 A / 3000 A 600 A / 6000 A
150 kW / 1.5 MW 300 kW / 3 MW 600 kW / 6 MW
Max. resolution W, VA, var 0.1 kW / 1kW 1 kW /10 kW 1 kW / 10 kW
Parameter   I17XX-FLEX1500 24 I17XX-FLEX3000 I17XX-FLEX6000
Active power (P) PF ≥ 0.99 150 A / 1500 A 300 A / 3000 A 600/6000 A
1,2 % + 0,005 % 1,2 % + 0,0075 % 1,7 % + 0,0075 %
Active energy Ea 0.1 ≤ PF ≤ 0.99 (1,2+√(1-PF2)/(2 PF)) % + 0.005 % (1,2+√(1-PF2)/(2 PF)) % + 0.0075% (1.7+√(1-PF2)/(2 PF)) % + 0.0075%
Apparent power S
Apparent energy Eap
0 ≤ PF ≤ 1 1,2 % + 0,005 % 1,2 % + 0,0075 % 1,7 % + 0,0075 %
Reactive power Q
Reactive energy Er
0 ≤ PF ≤ 1 2.5 % of measured apparent power/energy
Additional uncertainty
(% of power high range)
VP-N > 250 V 0,02 % 0,02 % 0,02 %
Phase (voltage to current) - 0,28° 0,28° 0,28°

1 Rated voltage in the range 100 V to 690 V; also known as Udin.

Reference conditionsEnvironment: 23 °C ± 5 °C, instrument in use for at least 30 minutes, no external electric/magnetic field, relative humidity <65 %

Input conditions: CosΦ/PF=1, sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ± 10%.

Power and supply specifications: Input voltage range > 100 V

Input current > 10% of current range

Primary conductor of terminals or Rogowski coil in centre position

Temperature coefficient: Plus 0.1 x the specified accuracy for each °C above 28 °C or under 18 °C

General specifications

Key features
Warranty Analyzer: 2 years (excluding battery)
Accessories: 1 year (battery included)
Calibration cycle 2 years
Dimensions (L x W x H) 28.0 cm x 19.0 cm x 6.2 cm (11.0 in x 7.5 in x 2.4 in)
Weight 2.1 kg
Anti-theft security Slot for Kensington lock
Environmental specifications
Operating temperature range -10 °C to 50 °C
Storage temperature range -20 °C to 60 °C
Relative humidity during operation IEC 60721-3-3: 3K5, modified:
-10 °C to 30 °C: ≤95%, no condensation or ice
35 °C: 70%
40 °C: 55 %
50 °C: 35 %
IP rating IEC 60529: IP50
Vibration resistance IEC 60721-3-3M2
Nutrition
Voltage range 100 V - 600 V -15% / +10% (85 V ... 660 V)
Power consumption Max. 40 VA
Mains frequency 50/60 Hz (42.5 Hz ... 69 Hz)
UPS Lithium-ion battery BP1770 with extended temperature range, customer-replaceable
Battery life: 1.5 hours
Safety
General IEC 61010-1: Pollution degree 2
Nutrition Overvoltage category IV 600 V
With mains adapter MA-C8: overvoltage category II 300 V
Measurement IEC 61010-2-030: CAT IV 600 V, CAT III 1000 V
Altitudes 2000 m to 4000 m Back scheme to:
Power supply: Category IV 300 V
With MA-C8 adapter: Category II 150 V
Measurement: CAT IV 300 V, CAT III 600 V, CAT II 1000 V

 