| Electrical specifications |
| Nutrition |
| Voltage range |
100 V to 500 V using protected plug-in input when current from the measured circuit is used |
| 100 V to 240 V MA-C8 when using standard power cord (IEC 60320 C7) |
| Power consumption |
Maximum 50 VA (max. 15 VA when connected to MA-C8 adapter) |
| Efficiency |
≥ 68.2% (in accordance with energy efficiency rules) |
| Maximum consumption without load |
< 0.3 W only when current is used via IEC 60320 input |
| Mains frequency |
50/60 Hz ±15% |
| Battery |
Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
| Battery life |
Normally four hours |
| Charging time |
< 6 hours |
| Data acquisition |
| Resolution |
16-bit synchronous sampling |
| Sample frequency |
10.24 kHz at 50/60 Hz, synchronised with frequency of mains supply |
| Input signal frequency |
50/60 Hz (42.5 to 69 Hz) |
| Circuit types |
1- Φ, 1- Φ IT, split phase, 3- Φ triangle, 3- Φ star, 3- Φ star IT, 3- Φ star symmetrical, 3- Φ Aron/Blondel (2-element triangle), 3- Φ triangle open lay, flows only (load studies) |
| Data storage |
Internal Flash memory (cannot be replaced by the user) |
| Memory |
Normal 20 log sessions of 4 weeks with 1-minute intervals and 500 events |
| Base interval |
| Measured parameters |
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
| Average interval |
User-selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
| Average time for minimum/maximum values |
Voltage, current: RMS full cycle updated every half cycle (URMS 1/2 according to IEC61000-4-30 Aux, power: 200ms) |
| Requirement interval (Energy meter mode) |
| Measured parameters |
Energy (Wh, varh, VAh), PF maximum requirement, energy cost |
| Interval |
User-selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off |
| Measurements mains power quality |
| Measured parameter |
Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage harmonics, TID V, current harmonics, TID A, flicker, mains signalling (signals superimposed on mains voltage), excessive/small deviation |
| Average interval |
10 min for all parameters
2 hours (prolonged flicker PLT)
150/180 cycles (3 s) for harmonics (requires IEEE519/REPORT software licence) |
| Individual harmonics |
2nd to 50th harmonics
Grouping according to IEC 61000-4-7 user-configurable depending on application: with subgroups (harmonics + interharmonics), grouped or only harmonic bins |
| Interharmonischen |
1st to 50th interharmonic |
| Total harmonic distortion |
Calculated at 50 voltage harmonics |
| Events |
Voltage: decreases, increases, interruptions, current: inrush current
1748: signals superimposed on mains voltage, transients (low frequency) |
| Triggered registrations |
RMS profile: Full RMS cycle every half voltage and current cycle updated to 11 s (URMS1/2 in accordance with IEC 61000-4-30) |
| Waveform of voltage and current up to 200 ms, 10/12 cycles |
| Signal superimposed on mains voltage: 10/12-cycle RMS recording of configured frequencies up to max. 120s |
| Inrush current |
RMS profile based on RMS of 1/2 cycle with stable triggering |
| Flicker |
Compliant with IEC 61000-4-15 and IEEE 1453 |
| Signals superimposed on the mains voltage (mains signalling) |
Two user-defined frequencies up to 3 kHz |
| PQ quality |
Summary of mains power quality in one table. Detailed data available for each parameter |
| EN 50160 |
Compliance with standard |
| Programmable PQ limits |
Enables user-defined limits for compliance with local standards |
| Compliance with standards |
| Harmonischen |
IEC 61000-4-7: Class 1 |
| IEEE 519 (short and very short harmonics) |
| Mains power quality |
IEC 61000-4-30 class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device) |
| Nutrition |
IEEE 1459 |
| Network power quality compliance |
EN 50160 |
| Safety |
General: IEC 61010-1, pollution degree 2 |
| Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V |
| Power supply: overvoltage category IV, pollution degree 2 |
| Li-ion battery: IEC 62133 |
| Interfaces |
| USB-A |
File transfer via USB flash drive, firmware updates, max Power supply current: 120 mA |
| WiFi |
File transfer and remote control via direct connection or WiFi |
| Bluetooth |
Reading additional measurement data from Fluke Connect® 3000 series modules (USB to BLE or WiFi/BLE adapter support required, check availability) |
| USB mini |
Downloading data to PC |
| Voltage inputs |
| Number of inputs |
4 (3 phases to neutral) |
| Maximum input voltage |
1000 Vrms, CF 1.7 |
| Input impedance |
10 MΩ |
| Bandwidth |
42.5 Hz to 3.5 kHz |
| Scale setting |
1:1 and variable |
| Measurement category |
1000 V CAT III/600 V CAT IV |
| Power inputs |
| Number of inputs |
4 (3 phases and neutral), mode is automatically selected for connected sensor |
| Input voltage |
Terminal input: 500 mVrms/50 mVrms; CF 2.8 |
| Rogowski coil input150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range |
| Reach |
1 A to 150 A/10 A to 1500 A with thin flexible current clamp i17XX-flex1500 IP 24 |
| 3 A to 300 A/30 A to 3000 A with thin flexible current clamp i17XX-flex3000 IP 24 |
| 6 A to 600 A/60 A to 6000 A with thin flexible current clamp i17XX-flex6000 IP 36 |
| 40 mA to 4 A/0.4 A to 40 A with 40 A terminal i40s-EL |
| Bandwidth |
42.5 Hz - 3.5 kHz |
| Scale setting |
1:1 and variable |
| Auxiliary inputs |
| Number of inputs |
2 (analogue with auxiliary adapter, or max. 2 BLE devices simultaneously) |
| Input range |
0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 readout/s |
| Scale factor |
Format: mx + b (gain and deviation) user-configurable |
| Displayed units |
User-configurable (7 characters, e.g. °C, psi, or m/s) |
| Bluetooth wireless connectivity (check availability) |
| Number of inputs |
2 |
| Supported modules |
Fluke Connect® 3000 series |
| Acquisition |
1 measurement/s |
| Environmental specifications |
| Operating temperature |
-25 °C to +50 °C (-13 °F to 122 °F)1 |
| Storage temperature |
Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F) |
| Relative humidity during operation |
IEC 60721-3-3: 3K6: |
| -25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 % |
| 40 °C (104 °F): 55 % |
| 50 °C (122 °F): 35 % |
| Operating height |
2000 m (maximum 4000 m reduce to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
| Height when stored |
12.000 m |
| Housing |
IEC 60529: IP50 |
| IEC 60529: IP65 with IP65 certified voltage connector |
| Vibration resistance |
IEC 60721-3-3M2 |
| Electromagnetic compatibility (EMC) |
EN 61326-1 Industrial CISPR 11: group 1, class A |
| IEC 61000-6-5 power plant environment |
| Korea (KCC): class A equipment (industrial transmission and communication equipment) |
| USA (FCC):47 CFR 15 subpart B. This product is considered an exempt device under clause 15.103. |
| General specifications |
| Warranty |
Two years (excluding battery) |
| Accessories: one year |
| Calibration cycle: two years |
| Dimensions |
23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in) |
| Weight |
Instrument: 1 kg (2.2 lb) |
| Protection against unauthorised operations |
Suitable for securing cables (max. Φ 6mm) |
| 1Warm up the product to -10 °C (+14 °F) before turning on the unit |
| Specifications i17XX-FLEX1.5KIP flexible current clamp |
| Measuring range |
1 to 150 A AC / 10 to 1500 A AC |
| Probe cable length |
610 mm (24 in) |
| Probe cable diameter |
7.5 mm (0.3 in) |
| Weight |
170 g (0.38 lb) |
| Minimum bending radius |
38 mm (1.5 in) |
| Non-destructive flow |
100 kA (50/60 Hz) |
Temperature coefficient over
the operating temperature range |
0.05% from readout/°C (0.028% from readout/°F) |
| Operating voltage |
1000 V CAT III, 600 V CAT IV |
| Output cable length |
2,0 m |
| Cable material |
TPR |
| Weight |
115 g |
| Cable material |
TPR |
| Material coupling |
POM + ABS/PC |
| Output cable |
TPR/PVC |
| Operating temperature |
-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor being tested shall not exceed 80 °C (176 °F) |
| Temperature, non-operating |
-40 °C to +80 °C (-40 °F to 176 °F) |
| Relative humidity, operating |
15% to 85%, non-condensing |
| Protection class |
IEC 60529: IP65 |
| Warranty |
One year |