The ideal tester for hard-working professionals.
This instrument is ideal for professional users - full functionality, advanced measurement capabilities, yet easy to use. Intuitive to operate and easy to master by field technicians of all levels.
Measuring functions
Other features
Memory interface
The ideal tester for hard-working professionals.
This instrument is ideal for professional users - full functionality, advanced measurement capabilities, yet easy to use. Intuitive to operate and easy to master by field technicians of all levels.
| Alternating voltage measurement | |
| Reach | 500 V |
| Resolution | 0,1 V |
| Accuracy 45 Hz - 66 Hz | 0,8% + 3 |
| Input impedance | 360 kΩ |
| Overload protection | 660 V RMS |
| Passage test (RLO) | |
| Measuring range (automatic range setting) | 20 Ω / 200 Ω / 2000 Ω |
| Resolution | 0.01 Ω / 0.1 Ω / 1 Ω |
| No-load voltage | >4 V |
| Insulation resistance measurement (RISO) | |
| Test voltages | 50-100-250-500-1000 V |
| Accuracy of test voltage (at rated test current) | +10%, -0% |
| Test voltage | 50 V 100 V 250 V 500 V 1000 V |
| Insulation resistance range | 20 MΩ /50 MΩ 20 MΩ / 100 MΩ 20 MΩ / 200 MΩ 20 MΩ / 200 MΩ / 500 MΩ 20 MΩ / 200 MΩ / 1000 MΩ |
| Resolution | 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ 0.01 MΩ / 0.1 MΩ / 1 MΩ |
| Test current | 1 mA at 50 kΩ 1 mA at 100 kΩ 1 mA at 250 kΩ 1 mA at 500 kΩ 1 mA at 1 MΩ |
| Loop and grid impedance (ZI) | |
| Reach | 10 Ω / 0.001 Ω / high-current MΩ mode |
| Resolution | 0.01 Ω / 0.1 Ω / 1 Ω |
| Expected earth fault current, PSC test | |
| Reach | 1000 A / 10 kA (50 kA) |
| Resolution | 1 A / 0.1 kA |
| Calculation | Expected ground fault current (PEFC) or expected short circuit current (PSC) is determined by dividing the measured mains voltage by the measured loop resistance (L-PE) or mains resistance (L-N), respectively. |
| Testing of earth leakage circuit breakers, tested types of earth leakage circuit breakers | ||
| Type of earth leakage switch | AC¹ G²,S³ |
|
| Model 1663 | A =”4″, AC¹, G²,S³ | |
| Comments | Reacts to AC ²General, no delay ³Time delay =”4″Responds to impulse signal =”5″Responds to flat DC signal |
|
| Switch-off time test (ΔT) | ||
| Power settings¹ | 10-30-100-300-500-1000 mA - VAR 10-30-100 mA |
|
| Factor | x ½, x 1 x 5 |
|
| Measuring range | Type G earth leakage switches | 310 ms 50 ms |
| Earth leakage switches type S | 510 ms 160 ms |
|
| Comments | ¹1000 mA only type AC 700 mA maximum type A in VAR mode VAR mode not available for type B. |
|
| RCD/FI tripping current measurement/rise test (IΔN) | ||
| Current range | 30% to 110% of rated current of RCCB¹ | |
| Step size | 10% of IΔN² | |
| Step time | Type G | 300 m/step |
| Type S | 500 m/step | |
| Measuring accuracy | ±5% | |
| Specified trip current ranges (EN 61008-1) | 50% to 100% for type AC 35% to 140% for type A (>10 mA) 35% to 200% for type A (≤10 mA) 50% to 200% for type B ²5% for type B |
|
| Comments | ¹30% to 150% for type A IΔN > 10 mA 30% to 210% for type A IΔN = 10 mA 20% to 210% for type B |
|
| Earth resistance test (RE) | ||
| Reach | 200 Ω / 2000 Ω | |
| Resolution | 0.1 Ω / 1Ω | |
| Frequency | 128 Hz | |
| Output voltage | 25 V | |
| Indication of phase sequence | ||
| Icon | Phase sequence indicator is active. | |
| General specifications | ||
| Dimensions (L x W x H) | 10 x 25 x 12.5 cm | |
| Weight (incl. batteries) | 1.3 kg | |
| Number and size of batteries | 6 AA batteries. | |
| Seal | IP-40 | |
| Safety | Complies with EN61010-1 ed. 2.0 (2001-02), UL61010, ANSI/ISA -s82.02.01 2000 and CAN/CSA c22.2 no. 1010 2nd ed. | |
| Overvoltage | CAT III / 500 V; CAT IV 300 V | |
| Performance | EN61557-1 to EN61557-7 2nd edition and EN61557-10 2nd edition | |