| General specifications |
| AC current via beak |
| Reach |
999,9 A |
| Resolution |
0,1 A |
| Accuracy |
2% ±5 digits (10 Hz to 100 Hz) |
| 2.5% ±5 digits (100-500 Hz) |
| Crest factor (50 Hz/60 Hz) |
3 at 500 A |
| 2.5 at 600 A |
| Add 2% for CF > 2 |
| Alternating current via flexible current clamp |
| Reach |
2500 A |
| Resolution |
0.1 A (≤ 600 A) |
| 1 A (≤ 2500 A) |
| Accuracy |
3% ±5 digits (5 - 500 Hz) |
| Crest factor (50/60 Hz) |
3.0 at 1100 A |
| 2.5 at 1400 A |
| 1.42 at 2500 A |
| Add 2% for CF > 2 |
| Position sensitivity |
|
|
i2500-10 Flex |
i2500-18 Flex |
| A |
|
|
| Distance from optimum |
0.5 inch (12.7 mm) |
1.4 inches (35.6 mm) |
| Error |
±0.5% |
±0.5% |
| B |
|
|
| Distance from optimum |
0.8 inch (20.3 mm) |
2.0 inches (50.8 mm) |
| Error |
±1.0% |
±1.0% |
| C |
|
|
| Distance from optimum |
1.4 inches (35.6 mm) |
2.5 inches (63.5 mm) |
| Error |
±2.0% |
±2.0% |
| Measurement uncertainty, assuming the primary conductor is in an optimal position, no external electric or magnetic field is present and the operating temperature range is not exceeded. |
| DC current |
| Reach |
600,0 A |
| Resolution |
0,1 A |
| Accuracy |
2% ±5 digits |
| AC voltage |
| Reach |
1000 V |
| Resolution |
0.1 V (≤600.0 V) |
| 1 V (≤1000 V) |
| Accuracy |
1.5% ±5 digits (20 Hz to 500 Hz) |
| DC voltage |
| Reach |
1000 V |
| Resolution |
0.1 V (≤600.0 V) |
| 1 V (≤1000 V) |
| Accuracy |
1% ±5 digits |
| mV DC |
| Reach |
500.0 mV |
| Resolution |
0.1 mV |
| Accuracy |
1% ±5 digits |
| Frequency via beak |
| Reach |
5.0 Hz to 500.0 Hz |
| Resolution |
0.1 Hz |
| Accuracy |
0.5% ±5 digits |
| Trigger level |
5 Hz to 10 Hz, ≥10 A |
| 10 Hz to 100 Hz, ≥5 A |
| 100 Hz to 500 Hz, ≥10 A |
| Frequency via flexible current clamp |
| Reach |
5.0 Hz to 500.0 Hz |
| Resolution |
0.1 Hz |
| Accuracy |
0.5% ±5 digits |
| Trigger level |
5 Hz to 20 Hz, ≥25 A |
| 20 Hz to 100 Hz, ≥20 A |
| 100 Hz to 500 Hz, ≥25 A |
| Resistance |
| Reach |
60 kΩ |
| Resolution |
0.1 Ω (≤600 Ω) |
| 1 Ω (≤6000 Ω) |
| 10 Ω (≤60 kΩ) |
| Accuracy |
1% ±5 digits |
| Capacity |
| Reach |
1000 μF |
| Resolution |
0.1 μF (≤ 100 μF) |
| 1 μF (≤ 1000 μF) |
| Accuracy |
1% ±4 digits |
| Mechanical specifications |
| Maximum voltage between any connection and earth |
1000 V |
| Batteries |
2 AA, NEDA 15A, IEC LR6 |
| Operating temperature |
-10 °C to +50 °C |
| Storage temperature |
-40 °C to +60 °C |
Relative humidity during operation -
non-condensing (< 10 °C) |
≤90% RH (at 10 °C to 30 °C) |
| ≤75% RH (at 30 °C to 40 °C) |
| ≤45% RH (at 40 °C to 50 °C) |
| Operating height |
3000 m |
| Height when stored |
12.000 m |
| Dimensions (L x W x H) |
249 x 85 x 45 mm |
| Weight |
395 g |
| Jaw-opening |
34 mm |
| Diameter flexible current clamp |
7.5 mm |
Cable length flexible current clamp
(from head to electronic connection) |
1,8 m |
| Safety |
IEC 61010-1, pollution degree 2 |
| IEC 61010-2-032: CAT III 1000 V / CAT IV 600 V |
| IEC 61010-2-033:CAT III 1000 V / CAT IV 600 V |
|
|
| Protection class |
IEC 60529: IP30, out of operation |
| RF certification, FCC ID |
T68-FBLE IC:6627A-FBLE |
| Electromagnetic compatibility (EMC) |
| International |
IEC 61326-1: Electromagnetic environment, portable equipment, IEC 61326-2-2 |
| CISPR 11: group 1, class A |
| Group 1: the equipment has deliberately generated and/or uses conductively coupled high-frequency energy required for the internal functioning of the equipment itself. |
| Class A: the equipment is suitable for use in all buildings except residential buildings and buildings directly connected to a low-voltage supply network for residential buildings. There may be potential problems in ensuring electromagnetic compatibility in other environments, due to conducted and radiated disturbances. If the equipment is connected to an object under test, emissions greater than the levels defined by CISPR 11 may occur. |
| Korea (KCC) |
Class A equipment (industrial transmission and communication equipment) |
| Class A: the equipment meets the requirements for industrial electromagnetic radiation equipment, and the seller and user should take this into account. This equipment is intended for use in business environments and is not intended for home use. |
| US (FCC) |
47 CFR 15 subpart B. This product is considered an exempt device under clause 15.103. |
| Temperature coefficients |
Plus 0.1 x the specified accuracy for each degree C above 28 °C or below 18 °C |