FLUKE 6200 6500 portable device tester

Producer: Fluke

Fluke makes testing portable devices easier

  • Dedicated key for each test, to enable one-touch testing
  • Preset pass/fail levels to save time
  • Large backlit display that is comfortable to read.
  • One power socket for connecting devices
  • Separate IEC socket for easy testing of mains and extension cables
  • Measurement leads are detachable, for quick replacement on site
  • Integral handle
  • USB port for data transfer
  • Integral QWERTY keyboard for fast data input
  • Additional USB memory function for backing up stored data and transferring data to a PC
  • Large backlit graphic display
  • Pre-programmed automatic test sequences for greater ease of use
  • Integral codes for installations, locations and descriptions for faster data processing
  • Memory viewing function for more on-site monitoring capabilities
  • USB port for data transfer
Category:

Run more tests every day

The Fluke 6500-2 PAT tester is a compact lightweight solution that works at the touch of a button. This instrument has brought a new dimension to automatic testing capabilities, helping you test more portable devices per day. The 6500-2 is designed to let you work faster, without compromising test results.

One-touch solution...

The pre-programmed test routines are performed at the touch of a button. This simplifies testing and also enables faster, more efficient operation. The fully automatic 6500-2 also allows the user to define his/her own test routines, and features a QWERTY keyboard for fast data entry.

Light...

The 6500-2 weighs only about 3 kg; it is therefore light and therefore easy to carry when working on site. The robust carrying case (included) not only provides protection during transport, but also additional storage space for accessories and other instruments.

Small...

In addition, this portable equipment tester is also extremely compact and as robust as you have come to expect from Fluke, making it suitable for on-site work. A Fluke PAT tester comes with all the features you need for portable equipment testing, making it a complete all-in-one solution.

Specifications
Test specifications Display range accuracy is defined as ±(% of reading + number of counts) at 23 °C ±5 °C, ≤75% RH.
Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy (0.1 x specified accuracy) per °C may deteriorate.
The accuracies for the measuring ranges comply with standards EN61557-1: 1997, EN61557-2: 1997, EN61557-4: 1997, EN61557-6: 1997, DIN VDE0404-2.
Switch-on test When switched on, the tester shows an interrupted safety ground connection and measures mains voltage and frequency.
Display range 90 V to 264 V
Accuracy at 50 Hz ± (2% + 3 counts)
Resolution 0,1 V
Input impedance > 1 MΩ // 2.2 nF
Maximum mains input voltage 264 V
Protection line test (R pe) Display range 0 to 19.99 Ω
Accuracy (after test lead compensation) ± (2.5% + 4 counts)
Resolution 0,01 Ω
Test current 200 mA AC -0% +40% in 1.99 Ω
25 A AC ± 20% in 25 mΩ at 230 V
No-load voltage > 4 V AC, < 24 V AC
Test lead compensation for protective conductor test Can subtract up to 1.99 Ω
Insulation test (R iso) Display range 0 to 299 MΩ
Accuracy ± (5% + 2 counts) from 0.1 to 300 MΩ
Resolution 0.01 MΩ (0 to 19.99 MΩ)
0.1 MΩ (20 to 199.9 MΩ)
1 MΩ (200 to 299 MΩ)
Test voltage 500 V DC -0% + 25% at 500 kΩ load or 250 V DC -0% +25% at 250 kΩ load
Test current > 1 mA at 500 kΩ load, < 15 mA at 0 Ω
Auto-discharge time < 0.5 s for 1 μF
Max. Capacitive load Operates up to 1 μF
Touch current test Display range 0 to 1.99 mA AC
Accuracy ± (4% + 2 counts)
Resolution 0.01 mA
Internal resistance (via probe) 2 kΩ
Measurement method Probe*
Replacement leakage current test Display range 0 to 19.99 mA AC
Accuracy ± (2.5% + 3 counts)
Resolution 0.01 mA
Test voltage 100 V AC ± 20%
Load/leakage current test: load current Display range 0 A to 16 A
Accuracy ± (4% + 2 counts)
Resolution 0,1 A*
Load/leakage current test: load current Display range Mains voltage 230 V 0.0 VA to 3.7 kVA
Accuracy ± (5% + 3 counts)
Resolution 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)*
Load/leakage current test Display range 0 to 19.99 mA
Accuracy ± (4% + 4 counts)
Resolution 0.01 mA*
PELV test Accuracy at 50 Hz ± (2% + 3 counts)
Surge protector 300 V RMS
Alert threshold 25 V RMS
RCCB test: tripping current Usage measurement error ±10%
Nominal 30 mA
Accuracy ±5%
Earth leakage switch test: tripping time Standard requirement 61557 part 6; tolerance of nominal test current 0% to +10%
Usage measurement error ±10%
Type of earth leakage switch Universal AC 30 mA
Display range 310 ms
Resolution 0.1 ms
Accuracy 3 ms
Limit value for tripping time at 100% (30 mA) 300 ms
Limit switch-off time at 500% (150 mA) 40 ms
*The device under test is powered from the mains.

 

Environmental specifications
Operating temperature 0 to 40 °C
Relative humidity Non-condensing < 10 °C
95% from 10 to 30 °C
75% from 30 to 40 °C

 

Safety specifications
Safety specification Complies with EN61010-1 3rd edition
CAT II, 300 V, pole 2

 

Mechanical and general specifications
Dimensions 200 mm (L) x 275 mm (W) x 114 mm (H)
Weight 3.13 kg
Nutrition 230 V +10% -15%, 50 Hz ±2 Hz or (6500-2 only: 110 V +10% -15%,50 Hz ±2 Hz)
Power consumption (tester) Normal 13 W (idle)
Max. 60 W during protective conductor test with 25 A
Storage Temperature -10 to 60 °C
Corrosion resistance 70 °C at 95% RH for max. 5 days
Operating height 0 to 2000 m
Seal IP-40 (housing), IP-20 (connectors)
EMC Complies with EN61326-1, portable
EMI insensitivity 3 V/m